After logging in to the MMI, the Main Manu is displayed.

================ Main Menu ==============
ElecSys(V:5.7.2017-07-24-1300)  Wed Jul 26 22:20:20 2017
UnitName : 1 @ 192.3.1.10  REDIGATE  <40170-0118>-SerialNumb
---------------------------------------------
 1) System      Services
 2) Directory   Services
 3) Diagnostics Services

99 Log Off

Make selection:

...

Main Menu → System Services

The System Services menu is used to restart the system, change the system clock, view the status or enable/disable certain RediGate processes.

Enter 1 at the Main Menu for the System Services menu.

================ System Services ==============
ElecSys(V:5.7.2017-07-24-1300)  Wed Jul 26 22:47:52 2017
UnitName : 1 @ 192.3.1.10  REDIGATE  <40170-0118>-SerialNumb
---------------------------------------------
 1) Boot/Reconfigure     2) Set Clock
 3) Channel Status       4) Channel Enable/Disable
 5) Channel Scan         6) Single Poll
 7) RTU Enable/Disable   8) RTU Scan
 9) RPN Calculator      10) New Master Key
11) Read Handshake Pins 12) Write Handshake Pins
13) Run Custom Utility  14) MQttClient to Next Broker
15) Cell Modem Diags

Make selection:

...

Main Menu → Directory Services

The Directory Services menu is used for various file operations within the RediGate file system.

Enter 2 at the Main Menu for the Directory Services menu.

================ Directory Services ==============
ElecSys(V:5.7.2017-08-07-1200)  Thu Aug 17 06:32:10 2017
UnitName : 1 @ 192.3.1.10  REDIGATE  <46247-0004>-SerialNumb
---------------------------------------------
 1) Executables            2) Current Configs
 3) Download Directory     4) Put File to Remote
 5) Get File From Remote   6) Rename File
 7) Delete File in Remote  8) Delete IsaGraf Files
 9) View Zombie.log       10) IsaGraf App Info
11) Restore Previous UFF  12) View UFF Processing Details
13) View Load-Store File  14) View kernel or message logs
15) MQtt XML Information  16) View customer settings
17) ZMODEM File to Remote 18) ZMODEM File from Remote
19) View Problem.txt      20) View ModemLog.txt
21) Store-N-Forward File

Make selection:

 

1- Executables

Main Menu → Directory Services → Executables

...

Make selection: 19
Press 'Q' to quit, SPACE-BAR for next page
Sun Aug 27 15:44:48 CDT 2017

Multiple .xml.gz files cannot be translated
test1.xml.gz  and  test2.xml.gz

Sun Aug 27 15:51:25 CDT 2017
/home/director/2017-08-07-1200-redigate_7_3.15_32.tar.gz was not tagged for REDIGATE
Press ENTER...

20- View ModemLog.txt

...

→AT+CSQ...OK
<-+CSQ: 13,99\r\n\r\nOK
→ATDT#777...CONNECT
←CONNECT
Running pppd /dev/ttyEMUX0 230400 file /dev/null modem crtscts lock asyncmap 0 nodetach nodefaultroute noauth usepeerdns
Using interface ppp0
Connect: ppp0 <--> /dev/ttyEMUX0
local  IP address 75.242.97.94   
(The Local IP address indicates a successful connection and the RediGate's address on the cellular network.) 
remote IP address 66.174.62.1
primary   DNS address 198.224.147.135
secondary DNS address 198.224.146.119
Press ENTER...

21- Store-N-Forward File

Main Menu → Directory Services → Store-N-Forward

...

Make selection: 21

================ Store and Forward Files ==============
ElecSys(V:5.7.2017-08-24-1000)  Wed Sep  6 16:35:43 2017
RediGate120E : 1 @ 0.0.0.0  REDIGATE  <46247-0002>-SerialNumb
---------------------------------------------
0=/tmp/sdcard1 : 1=/tmp/usb1 : 2=Edit Last Reported Times

Select folder (0,1)? 0

Enter0to select the /tmp/sdcard1 location, then enter the folder name containing the archive files.

Gateway.json  SNF14_00003   SNF15_00003   SNF_HELP.txt
SNF00_00001   SNF15_00002   SNF15_00004

Enter Directory name (e.g. SNF00_00001) SNF00_00001
-rwxr-xr-x    1 root     root           241 Oct  4  2016 MastChan0~Micro820~20161004CHAN00~RTU-1~20161004.csv
-rwxr-xr-x    1 root     root         16021 Oct  6  2016 MastChan0~Micro820~20161006CHAN00~RTU-1~20161006.csv
-rwxr-xr-x    1 root     root        428984 May 22 20:35 MastChan0~Micro820~20170522CHAN00~RTU-1~20170522.csv

Enter name if File to View  MastChan0~Micro820~20170522 CHAN00~RTU-1~20170522.csv

After entering the file name, the file will be displayed one page at a time. Press the Space bar to page through the file, or enter  Q  to quit the display.

Comma-separated values are shown, following a CSV header. The header columns are:

  • EpochTime is the timestamp of data in seconds since 1/1/1970 (32-bit integer, based on the system clock at the time); or if the Pacing is set to 0, the column will be EpochTimeMS (a 64-bit integer containing milliseconds since 1/1/1970).
  • RegAddr_OR_TagName is either the RTDB register number, or the Tag name if configured for that register.
  • Delivered is 1 if the data has already been published to MQTT, or 0 if not published.
  • GoodQuality is 1 is the point quality status at the time it was logged (1=online, 0=offline).
  • DataType is the type enumeration of the register (1=Boolean, 2=CHAR, 3=UINT8, 4=SINT16, 5=UINT16, 8=SINT32, 9=UINT32, 10=REAL32, 11=STRING-32, 12=STRING-256, 15=REAL64, 16=SINT64, 17=UINT64).
  • Value is the register value at the time it was logged. String data might include commas, which would appear as additional CSV columns.

Below is an example of the content of the CSV file containing historical values using EpochTime

...

q

(seconds). The data header is stored in the CSV file every time the connection goes from connected to disconnected state.
This example shows tag names CycleCount, TankLevel, and PumpStatus, and an untagged register address 40001.
The Delivered column is 1=Published or 0=Unpublished. (This value is only saved at the time the data originally stored and is not updated once the historical data is subsequently published.)
The GoodQuality column indicates the Quality flag of the RTDB register at the time it was stored.
The DataType column is 1=Boolean, 5=UINT16, 9=UINT32, 10=REAL32.
The Value column shows the value in the data type. Boolean values are 0 or 1.

EpochTime,RegAddr_OR_TagName,Delivered,GoodQuality,DataType,Value
1495429200,CycleCount,1,1,9,910722733
1495429214,40001,1,1,5,65535
1495429220,TankLevel,1,1,10,4.0
1495429224,CycleCount,0,1,9,910729218
1495429229,CycleCount,0,1,9,910731378
1495429235,PumpStatus,0,1,1,1

Below is an example with the content of the CSV file containing historical value using EpochTimeMS (milliseconds).

EpochTimeMS,RegAddr_OR_TagName,Delivered,GoodQuality,DataType,Value
1529675863415,40001,0,1,8,1529675863
1529675863415,40002,0,1,8,367

 

The Store & Forward process keeps track of the date of the last-reported historical record value. Upon reconnected link status of the monitored process, it will begin at this timestamp to publish additional historical values.

You can change the last-reported time to skip forward and not publish some records, or to skip backward and republish older historical records.

From the Directory Services menu option 21, select 2 to Edit Last Reported Times.

Make selection: 21

================ Store and Forward Files ==============
ElecSys(V:5.7.2017-08-24-1000)  Wed Sep  6 16:35:43 2017
RediGate120E : 1 @ 0.0.0.0  REDIGATE  <46247-0002>-SerialNumb
---------------------------------------------
0=/tmp/sdcard1 : 1=/tmp/usb1 : 2=Edit Last Reported Times

Select folder (0,1 or 2)? 2

Enter the Channel Number and Field Unit Address of a unit to change the Store & Forward last-reported date/time.

Chan Name              Status    Rtus Time
==== ==============    ========  ==== ==================
   0 CHAN00            Normal       2  Mon Jul 23 12:27:10 2018
   2 Master Channel    Normal       1  Thu Jul 19 15:16:14 2018
Enter Channel Number (0-15) 0

 
  -----------------RTU----------------   -----POLL-------  -------ERRORS-------
 Addr Name             Protocol Status     Time     Count  TimOut BadData Frame
----- ---------------- -------- -------- -------- -------- ------ ------- -----
    1 RTU-1            SOSMST00 PollDone 12:27:14    57304      0       0    0
Enter Rtu Address (0 - 65535) 1

Enter a number of days (positive or negative) to adjust the current last-reported time for this Field Unit. Enter a whole number of days, or a fraction (such as  -0.5  to skip backward half a day, or  0.04167  to skip forward one hour).

Enter Y to accept the adjusted last-reported time.

Last CSV Time ==>  2018-10-28 12:00:04  LOCAL
DAYs forward (positive) or backward (negative) to adjust (e.g. 0.5 days) 0.04167
New CSV Time ===>  2018-10-28 13:00:04  LOCAL
Is this acceptable as the new reporting time? (y/n) y

 

...

3- Diagnostics Services Menu

...

 Addr Name             Dbg? Protocol Status
----- ---------------- ---- -------- ------
    1 DNP3 Field Unit  ON   DNPMST00 Timeout

Enter RTU Address (-1 for all) ? 1

Enter 0=Disable : 1=Enable [Default=1] ? 1

After entering all information related to the task Debug Level modification, a single line output will indicate the change in status, and the list of tasks will generally be shown again.

Setting Scan-Rtu 1 to Enable Dump

================ Channel Diags ==============
ElecSys(V:5.7.2017-08-07-1200)  Sun Sep  3 21:17:07 2017
UnitName : 1 @ 192.3.1.10  REDIGATE  <46247-0004>-SerialNumb
---------------------------------------------
Chan Name              Status    Rtus Time
==== ==============    ========  ==== ==================
   0 Channel0          w/Errors     1  Tue Dec 14 09:37:57 1999
   1 Channel0          w/Errors     1  Tue Dec 14 09:37:56 1999
  15 Channel15         Normal       1  Tue Nov 30 06:00:02 1999

Enter Channel (0 to 15) ?

Once you have modified the Debug level for all FieldUnits that you wish to change, press Enter to return to the Diagnostics Services menu, or enter another channel number.

Anchor
RTUStatus
RTUStatus
9- RTU Status

...

Linux Diagnostic Commands

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

...