NOTES ABOUT THE OMRON-FINS UDP PROTOCOL SUPPORT

Only implements UDP (default port is 9600) packets.
TCP/IP version of the protocol might be accomplished by linking into the RediGate/Director RediGate Terminal Client process.

The 'PLC FINS Node' can range from 1 to 254 and should match the last octet of the Ethernet Address of the PLC associated with the communications.

...

The 'SNA Src Network' is used for the Source Network Address where "0" is Local otherwise use values from 1 to 127.

The 'DirectorRediGate/RediGate FINS Node' parameter is used to set the Elecsys Unit's Node Address from 1 to 255 and should match the last IP OCTET address of the Ethernet card associated with the communications.

...

RTDB Address : This column configures the starting RTDB register address associated with the 'Cmd Code' data. The poll table used five digit Modbus address to identify the four major Modbus data areas… 1 to 9999 for Coils (RW), 10001 to 19999 for Discrete Inputs (RO), 30001 to 39999 for Input Registers (RO) and 40001 to 49999 for Holding Registers (RW). This configures where to begin storing data from the Omron Reply into the DirectorRediGate/RediGates's RTDB area. More info needed.

...