  1. Using ACE, Open the default config configuration you used in the "Getting Started Guide"
  2. Download and open Elecsys-AzureIoT-Demo.xml from the http://partner.elecsyscorp.com site within the same ACE window
  3. In your default configconfiguration, enable the DNS Client object by setting its Enabled checkbox.
    Image RemovedImage Added

  4. Disable Virtual Unit 3 by clearing its Enabled checkbox.


  5. Copy and paste the following objects from the Elecsys-AzureIoT-Demo.xml config into your default configconfiguration.
    1. TLS Tunnels  (paste under Networks)


    2. FieldUnitInternalMast2 (paste under NullCircuit)


    3. VirtualRW Unit 4 (paste under NullCircuit)


    4. Data Simulator (paste under Internal Channel 15)



    5. MQTT_Client (paste under Clients)


    6. Global Text (paste under Clients


    Include Page
    Renaming Nodes
    Renaming Nodes


  6. Copy Table data from the Elecsys-AzureIoT-Demo.xml Internal Channel 15 → Scan Table into your RediGate Configuration (in Internal Channel, open Scan Table, right-click and select Paste, over-write data). 


     

    Info
    titleScan Table Info

    The "Scan Table" object tells the RediGate which RTU (Unit 2, the data simulator) to run at an interval (Scan Period) which is set to every 600 seconds. This is how frequently the RediGate will check the data simulator for changes, which will result in data being published every 10 minutes. You can change this to whatever number you would like, however you will want to keep an eye on the number of messages published as Azure charges on a per message basis.

  7. Update your MQTT_Client properties to match the parameters in your Azure IoT Hub account:


    1. The ${GATEWAY} parameter references the System → Unit Name value, which in the default configuration is "RediGate120E".


    2. You will need to change your "System → Unit Name" property to match the "Device Id" of the registered device in the Azure IoT Hub. In the screenshot below, the device ID of "RediGate120E" matches that of the default configuration.

    3. The "MQTT_Client → User Name" property needs to match the "Hostname" property in Azure IoT Hub, followed by /deviceID at the end of the URL (in our case   /${GATEWAY}   since that is what we are using for our Device ID).


  8. Update the "TLS Tunnels → STUNNEL Parameters" property to match the "Hostname" property of your Azure IoT hub, followed by   :8883


  9. Use the Azure "Device Explorer Twin" software tool (https://github.com/Azure/azure-iot-sdks/releases/download/2016-11-17/SetupDeviceExplorer.msi) to create a SharedAccessSignature
    1. Find the "SharedAccessKey" for the "iothubowner" user in Azure.


    2. Enter the credentials into the "Connection Information" section on the "Device Explorer Twin". In this example, we use HostName=elecsysdev.azure-devices.net;SharedAccessKeyName=iothubowner;SharedAccessKey={iothubowner Primary Key from above}


  10. Once you have a successful connection in the "Device Explorer Twin", navigate to the "Management" tab and select the appropriate Device ID, press the "SAS Token" button, set the appropriate TTL (days of validity for the device key), and click "Generate"


  11. Copy the highlighted section below from your SASTokenForm beginning after the ";SharedAccessSignature=".  Paste into the first row of the "Global Text" object of your RediGate configuration, in the "Replacement Text" column.


  12. Upload configuration to your RediGate
  13. Confirm that data is being published every 10 minutes using the "Device Explorer Twin" Data tab:

...