RediGate Title Page Boilerplate

...

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

See RediGate 100 Hardware Manual#Certifications262157 for a list of certifications of the RediGate products. To ensure compliance with Electromagnetic Emissions Interference (EMI) standards, the user must install a ferrite on the Ethernet cable (see 262157).

...

Model

RediGate

Width

4.88” (12.40 cm)

Length

2.90“ (7.85 37 cm) (excluding connectors)

Height

1.35” (3.43 cm) (excluding DIN rail mount feet)

Weight

0.5 lbs (0.23 kg)

...

Feature

Certification

Test Method and Limits

Radiated Emissions

US CFR Title 47, FCC Part 15B
Canada’s ICES-003, Issue 6

EN 61000-6-4:2007/A1:2011
EN 55011:2009/A1:2010

FCC Part 15.109, Class A
ICES-003 Issue 7, Section 6.2
ANSI C63.4:2014, Section 8
EN 61000-6-4:2005/AC:2005
EN 55011:2009/A1:2010
EN 55032:2012/AC:2013
EN ETSI 301 489-1 V2.1.1
AS/NZS 32
VCCI 32
KDB 996369 (Module Integration Verification)

Conducted Emissions

US CFR Title 47, FCC Part 15B
Canada’s ICES-003, Issue 6

EN 61000-6-4:2007/A1:2011
EN 55011:2009/A1:2010

FCC Part 15.107, Class A
ICES-003 Issue 7, Section 6.1
ANSI C63.4:2014, Section 7
EN 61000-6-4:2005/AC:2005
EN 55011:2009/A1:2010
EN 55032:2012/AC:2013
EN ETSI 301 489-1 V2.1.1
AS/NZS 32
VCCI 32

Immunity

EN 61326-1:2013
EN ETSI 301 489-1 V2.1.1

Electrostatic Discharge: IEC 61000-4-2:2008; 4 kV/8 kV Contact/Air

Radiated Immunity:
IEC 61000-4-3:2006/A1:2007/A2:2010
3V/m, 80MHz – 1GHZ
3V/m, 1.4 – 2GHz;
3 V/m, 2-3GHz
3 V/m, 3-6GHz
80% amplitude modulation at 1kHz

EFT-I/O lines: IEC 61000-4-4:2004/A1:2010; ±1 kV

Surge-DC: IEC 61000-4-5:2014; ±0.5 kV

Conducted Immunity – I/O lines: IEC 61000-4-6:2014; 3 Vrms

Safety

UL 60950-1:2007
CAN/CSA C22.2#60950-1:2007

Conforms to IEC/EN 62368-1


Environmental

RoHS (EU Directive 2011/65/EC)

WEEE (EU Directive 2012/19/EU)


Hazardous Location

Class 1, Division 2, Groups A, B, C, and D, temp. T4

Conforms to ISA STD 12.12.01
Certified to CSA STD C22.22 #213


...