  1. Using ACE, Open the default config you used in the "Getting Started Guide"
  2. Download and open Modbus-TCP-Slave-Demo.xml from the the http://partnerredigate.elecsyscorp.com/examples/ site within the same ACE window

  3. Disable Virtual Unit 3 by clearing its Enabled checkbox.
  4. Copy and paste the following objects from the Elecsys-AWS-Demo.xml config into your default configuration:
    1. FieldUnitInternalMast2 (paste under NullCircuit)

    2. VirtualRW Unit 4 (paste under NullCircuit)
    3. Data Simulator (paste under Internal Channel 15)
    4. SlaveModbusTCP0 (paste under SlaveChannels)
  5. Update the EtherPort settings so that your RediGate is on the same network as the Modbus master device

  6. Update the firewall object to allow traffic on port 502 for the Ethernet port that the Modbus master connects to. In the screenshot below, we add port 502 to both the eth0 and eth1, allowing Modbus traffic on either port of our 120e

  7. Edit the "Internal Channel 15" object so that it contains a scan record for FieldUnitInternalMaster2 (Unit Address 2), poll record 1, with a Scan Period of 1 second:


...