3- Diagnostics Services Menu
...
================ Diagnostic Services ==============
ElecSys(V:5.7.2017-08-24-1000) Wed Sep 6 19:31:54 2017
RediGate120E : 1 @ 0.0.0.0 REDIGATE <46247-0002>-SerialNumb
---------------------------------------------
1) System Status 2) Network Interfaces
3) Run Time and Loading 4) System Resources
5) Task Status 6) Task Diags
7) Channel Status 8) Channel Diags
9) Rtu Status 10) Rtu Diags
11) Rtu Clear 12) Slave Diags
13) IP Route Table 14) Ping Service
15) RTDB Status 16) RTDB Diags
17) MQtt Status 18) RTDB Data Dump
19) Dial Backup 510) Trend a Point
535) View Custom Rpt
99) Monitor Diag's
Make selection
:
Anchor | ||||
---|---|---|---|---|
|
...
Make selection: 1
================ System Status ==============
ElecSys(V:5.7.2017-08-07-1200) Sun Sep 3 21:17:07 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb
---------------------------------------------
Linux UnitName 3.15.10-00073-ge03f088 #0 PREEMPT Thu Nov 20 10:42:18 CST 2014 armv5tel GNU/Linux
Press ENTER to continue
------ Message Queues --------
key msqid owner perms used-bytes messages
0x00000290 0 root 666 0 0
0x00002dc8 1409025 user 666 0 0
0x00000bed 720899 root 666 0 0
0x00000bf2 753668 root 666 0 0
0x00000bf6 786437 root 666 0 0
0x00000bfa 819206 root 666 0 0
0x00000bff 851975 root 666 0 0
0x00000c05 884744 root 666 0 0
0x00000c06 917513 root 666 0 0
0x00000c07 950282 root 666 0 0
0x00000c09 983051 root 666 0 0
0x00000c0c 1015820 root 666 0 0
0x00000c0e 1048589 root 666 0 0
0x00000c0f 1081358 root 666 0 0
0x00000c10 1114127 root 666 0 0
0x00000c12 1146896 root 666 0 0
0x00000c14 1179665 root 666 0 0
0x00000c16 1212434 root 666 0 0
0x00000c18 1245203 root 666 0 0
0x00000c19 1277972 root 666 0 0
0x00000c5f 1376277 root 666 0 0
0x00000c1a 1310742 root 666 0 0
0x00000c1b 1343511 root 666 0 0
Press ENTER to continuecontinue
2- Network Interfaces
Main Menu → Diagnostics Services → Network Interfaces
...
Info |
---|
NOTE that in older RediGate tarballs prior to September 2017, this menu only worked if you logged in as 'root' first, then superuser to the user account. |
Make Make selection: 2
================ Network Interfaces ==============
ElecSys(V:5.7.2017-08-07-1200) Sun Sep 3 21:17:07 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb---------------------------------------------
eth0 Link encap:Ethernet HWaddr 82:49:22:2B:82:A6
inet addr:10.63.191.28 Bcast:10.63.255.255 Mask:255.255.0.0
inet6 addr: fe80::8049:22ff:fe2b:82a6/64 Scope:Link
UP BROADCAST RUNNING MULTICAST MTU:1500 Metric:1
RX packets:19565659 errors:0 dropped:83411 overruns:0 frame:0
TX packets:77491 errors:0 dropped:0 overruns:0 carrier:0
collisions:0 txqueuelen:0
RX bytes:1376149850 (1.2 GiB) TX bytes:6030078 (5.7 MiB)
lo Link encap:Local Loopback
inet addr:127.0.0.1 Mask:255.0.0.0
inet6 addr: ::1/128 Scope:Host
UP LOOPBACK RUNNING MTU:65536 Metric:1
RX packets:412 errors:0 dropped:0 overruns:0 frame:0
TX packets:412 errors:0 dropped:0 overruns:0 carrier:0
collisions:0 txqueuelen:0
RX bytes:37684 (36.8 KiB) TX bytes:37684 (36.8 KiB)
ppp0 Link encap:Point-to-Point Protocol
inet addr:10.12.0.15 P-t-P:10.12.0.15 Mask:255.255.255.255
UP POINTOPOINT RUNNING NOARP MULTICAST MTU:1500 Metric:1
RX packets:11 errors:0 dropped:0 overruns:0 frame:0
TX packets:5 errors:0 dropped:0 overruns:0 carrier:0
collisions:0 txqueuelen:3
RX bytes:424 (424.0 B) TX bytes:61 (61.0 B)Do you want to see Socket Statuses (Y/N) ? y
Press SPACE to page forward...
Active Internet connections (servers and established)
Proto Recv-Q Send-Q Local Address Foreign Address State
tcp 0 0 0.0.0.0:22 0.0.0.0:* LISTEN
tcp 0 0 10.63.191.28:22 10.242.3.2:65199 ESTABLISHED
tcp 0 0 :::22 :::* LISTEN
Active UNIX domain sockets (servers and established)
Proto RefCnt Flags Type State I-Node Path
unix 14 [ ] DGRAM 2214 /dev/log
Press ENTER to continue..
.
...
Enter 3 for Run Time and Loading.
Make Make selection: 3
================ Run Time ==============
ElecSys(V:5.7.2017-08-07-1200) Sun Sep 3 21:17:07 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb---------------------------------------------
Local_Time Up_Time 0.0=IDLE => 1 min 5 min 15 min <= 1.00=BUSY
---------- ------- ----- ----- ------
18:47:04 up 11 days, 12:47, load average: 2.89, 3.35, 3.43
Press ENTER to continuecontinu
e
4- System Resources
Main Menu → Diagnostics Services → System Resources
...
Make selection: 4
================ System Resources ==============
ElecSys(V:5.7.2017-08-07-1200) Sun Sep 3 21:17:07 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb---------------------------------------------
System RAM (1k-blocks)
total used free shared buffers
Mem: 253988 23296 230692 0 0
-/+ buffers: 23296 230692
Swap: 0 0 0
System FLASH
Filesystem 1K-blocks Used Available Use% Mounted on
ubi0:rootfs 57476 22804 34672 40% /
devtmpfs 126872 0 126872 0% /dev
tmpfs 126992 0 126992 0% /dev/shm
tmpfs 126992 152 126840 0% /tmp
Press ENTER to continuecontinu
e
5- Task Status
Main Menu → Diagnostics Services → Task Status
View the Debug Level for all running processes in the RediGate code. The Debug Level is used for RediGate task logging and can be set using menu option 6 and others. Real-time diagnostics can be viewed using menu option 99 - Monitor Diagnostics.
Enter 5 for Task Status.
The tasks are numbered sequentially (referred to as "slot numbers"), starting from 0. The name following each task is the mnemonic that appears in the real-time view as events occur.
The word following the task name (Status, Display, Dump, etc.) indicates the current Debug Level of the task (see Debug Levels).
Tasks are marked with All, None, or Some, to indicate whether debugging is enabled/disabled for all or part of the units associated with that task.
Make selection: 5
================ Task Status ==============
ElecSys(V:5.7.2017-08-07-1200) Sun Sep 3 21:17:07 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb---------------------------------------------
13 PROCESSES
0 - WATCHDOG Status ( All) 7 - CH01XDBM Status ( All)
1 - CHANNL00 Status ( All) 8 - DNPMST01 Status ( All)
2 - CHANNL01 Status ( All) 9 - CHN01SCN Status ( All)
3 - CHANNL15 Status ( All) 10 - CH15XDBM Status ( All)
4 - CH00XDBM Status ( All) 11 - VIRTMS15 Status ( All)
5 - DNPMST00 Status ( All) 12 - CHN15SCN Status ( All)
6 - CHN00SCN Status ( All)
Redisplay (Y/N)
?
6- Task Diags
...
Set the Debug Level for a process. (You can also set Debug Levels by using option 8 for Master Channel diagnostics, 10 for Field Unit protocol diagnostics, 12 for Slave Channel diagnostics, or 16 for RTDB diagnostics.) Use option 99 - Monitor Diagnostics to observe the real-time diagnostics of each task after setting the Debug Levels.
...
Make selection: 6
================ Task Diagnostics ==============
ElecSys(V:5.7.2017-08-07-1200) Sun Sep 3 21:17:07 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb---------------------------------------------
13 PROCESSES
0 - WATCHDOG Status ( All) 7 - CH01XDBM Status ( All)
1 - CHANNL00 Status ( All) 8 - DNPMST01 Status ( All)
2 - CHANNL01 Status ( All) 9 - CHN01SCN Status ( All)
3 - CHANNL15 Status ( All) 10 - CH15XDBM Status ( All)
4 - CH00XDBM Status ( All) 11 - VIRTMS15 Status ( All)
5 - DNPMST00 Status ( All) 12 - CHN15SCN Status ( All)
6 - CHN00SCN Status ( All)
Task Slot Number (0 to 12) ?
5
First, enter the Task Slot Number from the numbers that are listed. Depending on the task you have selected, you will have to enter a number of other information, starting with the new Debug Level that you wish to enable. NOTE: The Debug Level is GLOBAL for this task. The Debug Level ; i.e., it applies to all units (Node Addresses) associated with this task. If you wish to enable debugging for only one (or more) Field Unit or Node Address on a task, see NOTE below for Enable/Disable.
Task DNPMST00 Status ( All)
Valid Debug Level:
0 - Fatal Errors (Ending)
1 - General Errors (Error)
2 - Status Messages (Status)
3 - Data Display (Display)
4 - Data Dump (Dump)
Debug Level 0-4 or 'S'tats ?
4
If prompted, enter a Node Address within the task to which the diagnostics status will be applied. For master protocol tasks, this will be the Unit Field Unit Address of the device being monitored. For other task types, other information will be prompted to identify the scope of the diagnostic level being applied.
Enter Node Address for Slot=5 (-1 for all) 1
If prompted, enter 1 to enable the diagnostics for the task, or 0 to disable diagnostics .Note that the multiple debug items for same task can in some cases have diagnostics for multiple items for the Node Address (or All).
Enter 0=Disable : 1=Enable [Default=1] ? 1
Note | ||
---|---|---|
| ||
NOTE: If a task controls multiple Node Addresses (such as Field Units) |
...
, diagnostics for each Node Address can be enabled or disabled separately. One or more units may have debugging enabled simultaneously—enabling diagnostics for a single unit does not automatically disable diagnostics for all the others. For instance, to enable diagnostics for only 3 out of 10 Field Units on a master channel, first Disable diagnostics for "All" units; then select the Task Diagnostics menu multiple times to Enable diagnostics for only certain Field Unit node addresses. |
...
The last Debug Level selected applies to ALL enabled units controlled by this task. |
After entering all information related to the task Debug Level modification, a single line output will indicate the change in status, and the list of tasks will generally be shown again.
Setting DNPMST00 to Level Dump
13 PROCESSES
0 - WATCHDOG Status ( All) 7 - CH01XDBM Status ( All)
1 - CHANNL00 Status ( All) 8 - DNPMST01 Status ( All)
2 - CHANNL01 Status ( All) 9 - CHN01SCN Status ( All)
3 - CHANNL15 Status ( All) 10 - CH15XDBM Status ( All)
4 - CH00XDBM Status ( All) 11 - VIRTMS15 Status ( All)
5 - DNPMST00 Dump Dump ( All) 12 - CHN15SCN Status ( All)
6 - CHN00SCN Status ( All)
Task Slot Number (0 to 12)
?
...
- Master Channel number from configuration
- Master Channel name from configuration
- Current channel status (see Master Channel Status Indications for a list of status values)
- Number of Field Units (RTUs) configured on the channel
- System timestamp of the last event on the channel.
Make selection: 7
================ Channel Status ==============
ElecSys(V:5.7.2017-08-07-1200) Sun Sep 3 21:17:07 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb---------------------------------------------
Chan Name Status Rtus Time
==== ============== ======== ==== ==================
0 Channel0 w/Errors 1 Sat Dec 11 19:34:32 1999
1 Channel1 w/Errors 1 Sat Dec 11 19:34:33 1999
15 Channel15 Normal 1 Tue Nov 30 06:00:02 1999
Redislay (Y/N/D where D is Debug List)
?
...
- FieldUnit Address from configuration
- FieldUnit Name from configuration
- Status of debugging (enabled or disabled) for the FieldUnit
- Protocol enumeration as it appears in the Task List
- Status (see RTU Status for a list of these indications)
Redislay (Y/N/D where D is Debug List) ? d
Enter a Channel Number (0 to 15) ? 0
Addr Name Dbg? Protocol Status
----- ---------------- ---- -------- ------
1 DNP3 Field Unit ON DNPMST00 Timeout
Press ENTERENTE
R
Master Channel Status Indications
...
Enter 8 for Channel Diags. Enter the number of the Master Channel or Internal Channel for the FieldUnit that you want to change Debug Level. (See Master Channel Status Indications for a list of status values.)
Make selection: 8
================ Channel Diags ==============
ElecSys(V:5.7.2017-08-07-1200) Sun Sep 3 21:17:07 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb---------------------------------------------
Chan Name Status Rtus Time
==== ============== ======== ==== ==================
0 Channel0 w/Errors 1 Tue Dec 14 09:37:32 1999
1 Channel0 w/Errors 1 Tue Dec 14 09:37:31 1999
15 Channel15 Normal 1 Tue Nov 30 06:00:02 1999
Enter Channel (0 to 15) ?
0
Enter the new Debug Level that you wish to enable for this FieldUnit.
Valid Debug Level:
0 - Fatal Errors (Ending)
1 - General Errors (Error)
2 - Status Messages (Status)
3 - Data Display (Display)
4 - Data Dump (Dump)
Debug Level 0-4 ?
4
...
Addr Name Dbg? Protocol Status
----- ---------------- ---- -------- ------
1 DNP3 Field Unit ON DNPMST00 Timeout
Enter RTU Address (-1 for all) ? 1
Enter 0=Disable : 1=Enable [Default=1] ?
1
After entering all information related to the task Debug Level modification, a single line output will indicate the change in status, and the list of tasks will generally be shown again.
Setting Scan-Rtu 1 to Enable Dump
================ Channel Diags ==============
ElecSys(V:5.7.2017-08-07-1200) Sun Sep 3 21:17:07 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb---------------------------------------------
Chan Name Status Rtus Time
==== ============== ======== ==== ==================
0 Channel0 w/Errors 1 Tue Dec 14 09:37:57 1999
1 Channel0 w/Errors 1 Tue Dec 14 09:37:56 1999
15 Channel15 Normal 1 Tue Nov 30 06:00:02 1999
Enter Channel (0 to 15)
?
Once you have modified the Debug level for all FieldUnits that you wish to change, press Enter to return to the Diagnostics Services menu, or enter another channel number.
Anchor | ||||
---|---|---|---|---|
|
...
Enter 9 for RTU Status. Enter the Master Channel number to view Channel, Circuit, and Field Unit status. Or enter -1 to view the status for units on all channels.
(See Master Channel Status Indications for a list of status values.)
================ Rtu Status ==============
ElecSys(V:5.7.2017-08-07-1200) Mon Aug 14 02:10:12 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb
---------------------------------------------
Chan Name Status Rtus Time
==== ============== ======== ==== ==================
0 Channel0 Normal 3 Mon Aug 14 02:10:07 2017
2 Master Channel w/Errors 1 Mon Aug 14 02:02:14 2017
15 Channel15 Normal 1 Mon Aug 14 02:02:14 2017
Enter Channel (0 to 15, -1 for all) ? 0
-----------------RTU---------------- -----POLL------- -------ERRORS-------
Addr Name Protocol Status Time Count TimOut BadData Frame
----- ---------------- -------- -------- -------- -------- ------ ------- -----
1 Modbus01 MBMAST00 PollDone 02:10:07 9 2 0 0
2 Modbus02 MBMAST00 Timeout 02:09:15 0 9 0 0
3 Modbus03 MBMAST00 Polling 02:09:15 7 2 0 0
Redisplay (Y/N/E where E is Extended Info)
?
See Channel Status for details on the Master Channel status information.
...
- Addr – FieldUnit address from configuration
- Name – FieldUnit name from configuration
- Protocol – Enumeration indicating both the protocol and Master Channel instance number. For example, MBMAST00 refers to Modbus Master protocol on Channel 0. The Protocol enumeration is also used for diagnostic messages in the Monitor Diagnostics log.
- Status – Current state of each Field Unit.
- PollDone - Device is in communication and last poll was completed successfully.
- Timeout - Last poll to device timed out with no valid response.
- BadData - Last poll received some data but it was not a correct expected response (including an exception code).
- FrameErr - Last poll received a framing error (possibly part of the message was received but not all – ?? check with John)
- Stopped - Field Unit or Channel is disabled or not being polled
- Polling - Poll has been sent but response not yet received, or a response to one poll has been received but not all polls are completed, so the device status cannot be completely confirmed yet.
- No Polls - No polls have been sent to Field Unit since last restart.
- Time – Last time the Field Unit was accessed (started, polled, command sent).
- Count – Number of polls which have successfully received a response.
- TimOut – Number of polls which have timed out after all configured retries.
- BadData – Number of polls which have received a bad data response.
- Frame – Number of polls which have received a framing error response.
...
Redisplay (Y/N/E where E is Extended Info) ? e
Attempts_Per_Poll
Add Unit Dbg Circuit Last Clear Boot Type Port
----- -------------- --- ------- ---- ----- ---- ----- ----
1 Modbus01 ON CONNECT 1 1.0 1.0 TCP/IP 192.3.1.11:3040
2 Modbus02 ON CONNECT 4 4.0 4.0 DIRECT COM02 19200 NONE
3 Modbus03 ON CONNECT 1 1.0 1.0 TCP/IP 192.3.1.11:3040
Press ENTER...
The Address and Field Unit name are the same as above. Other circuit information is given for each device.
...
Enter 10 for RTU Diags. Enter the number of the Master Channel or Internal Channel for the FieldUnit that you want to change Debug Level.
(See Master Channel Status Indications for a list of status values.)
Make selection: 10
================ Rtu Diags ==============
ElecSys(V:5.7.2017-08-07-1200) Mon Aug 14 02:10:12 2017
UnitName : 1 @ 192.3.1.10 REDIGATE <46247-0004>-SerialNumb
---------------------------------------------
Chan Name Status Rtus Time
==== ============== ======== ==== ==================
0 Channel0 Normal 3 Mon Aug 14 02:10:07 2017
2 Master Channel w/Errors 1 Mon Aug 14 02:02:14 2017
15 Channel15 Normal 1 Mon Aug 14 02:02:14 2017
Enter Channel (0 to 15, -1 for all) ?
0
...
NOTE: the Debug Level applies to all Field Units of the same protocol under this Master Channel. (To see diagnostics for only some Field Units on a channel, you must disable diagnostics on the other units.)
Valid Debug Level:
0 - Fatal Errors (Ending)
1 - General Errors (Error)
2 - Status Messages (Status)
3 - Data Display (Display)
4 - Data Dump (Dump)
Debug Level 0-4 ?
4
Enter the FieldUnit Address to enable at the above diagnostics level, or -1 for all FieldUnits on the channel.
...
Setting Prot-Rtu 1 to Enable Dump
Valid Debug Level:
0 - Fatal Errors (Ending)
1 - General Errors (Error)
2 - Status Messages (Status)
3 - Data Display (Display)
4 - Data Dump (Dump)
Debug Level 0-4
?
...
Make selection: 11
================ Rtu Clear ==============
ElecSys(V:5.7.2017-08-24-1000) Mon Dec 6 05:15:36 1999
DNPMastTest : 1 @ 10.63.191.28 REDIGATE-400 <38258-0025>-SerialNumb
---------------------------------------------
Chan Name Status Rtus Time
==== ============== ======== ==== ==================
0 Channel0 Normal 1 Mon Dec 6 05:15:33 1999
1 Channel0 Normal 1 Mon Dec 6 05:15:34 1999
15 Channel15 Normal 1 Tue Nov 30 06:00:02 1999
Enter Channel (0 to 15) ? 0
Clear All Rtus (Y/N) ? n
-----------------RTU---------------- -----POLL------- -------ERRORS-------
Addr Name Protocol Status Time Count TimOut BadData Frame
----- ---------------- -------- -------- -------- -------- ------ ------- -----
1 DNP3 Field Unit DNPMST00 PollDone 05:15:39 111713 30 0 0
Enter Rtu to Clear ? 1
Clearing Rtu 1 Status Counters
Clear All Rtus (Y/N)
?
...
Make selection: 12
================ Slave Status/Diagnostics ==============
ElecSys(V:5.7.2017-08-30-1300) Mon Dec 6 05:18:07 1999
powirv : 1 @ 10.63.191.29 ZEUS-3.12 <Use System Serv Option-123>
---------------------------------------------
0 - DNPSLAV0 Status ( All) 1 - DNPSLAV1 Status ( All)
2 - DNPSLAV2 Status ( All) 3 - DNPSLAV3 Status ( All)
4 - MBNSL00d Status ( All) 5 - MBNSL001 Status ( All)
Task Slot Number (0 to 4) ? 0
Task DNPSLAV0 Status ( All)
Valid Debug Level:
0 - Fatal Errors (Ending)
1 - General Errors (Error)
2 - Status Messages (Status)
3 - Data Display (Display)
4 - Data Dump (Dump
)
...
Debug Level 0-4 or 'S'tatus ? s
Slave Status
Poll Received=3559767
Response Sent=49964436
Last Poll @ Mon Dec 6 05:18:13 2016
Numb Attachments=1
SlaveID=1 From: Chan=15 Rtu=3
Serial Port COM0 @ 0 baud
Press ENTER
================ Slave Status/Diagnostics ==============
ElecSys(V:5.7.2017-08-30-1300) Mon Dec 6 05:18:18 1999
powirv : 1 @ 10.63.191.29 ZEUS-3.12 <Use System Serv Option-123>
---------------------------------------------
0 - DNPSLAV0 Status ( All) 1 - DNPSLAV1 Status ( All)
2 - DNPSLAV2 Status ( All) 3 - DNPSLAV3 Status ( All)
4 - MBNSL00d Status ( All) 5 - MBNSL001 Status ( All
)
...
Task Slot Number (0 to 4) ? 0
Task DNPSLAV0 Status ( All)
Valid Debug Level:
0 - Fatal Errors (Ending)
1 - General Errors (Error)
2 - Status Messages (Status)
3 - Data Display (Display)
4 - Data Dump (Dump)
Debug Level 0-4 or 'S'tatus ? 4
Enter 0=Disable : 1=Enable [Default=1] ? 1
Setting DNPSLAV0 to Level Dump
================ Slave Status/Diagnostics ==============
ElecSys(V:5.7.2017-08-30-1300) Mon Dec 6 05:18:48 1999
powirv : 1 @ 10.63.191.29 ZEUS-3.12 <Use System Serv Option-123>
---------------------------------------------
0 - DNPSLAV0 Dump ( All) 1 - DNPSLAV1 Status ( All)
2 - DNPSLAV2 Status ( All) 3 - DNPSLAV3 Status ( All)
4 - MBNSL00d Status ( All) 5 - MBNSL001 Status ( All)
Task Slot Number (0 to 4)
?
...
Make selection: 13
================ Route Table ==============
ElecSys(V:5.7.2017-08-24-1000) Mon Dec 20 05:07:14 1999
DNPMastTest : 1 @ 10.63.191.28 REDIGATE-400 <38258-0025>-SerialNumb
---------------------------------------------
Kernel IP routing table
Destination Gateway Genmask Flags Metric Ref Use Iface
0.0.0.0 10.63.255.128 0.0.0.0 UG 0 0 0 eth0
10.53.47.0 0.0.0.0 255.255.255.0 U 0 0 0 eth3
10.63.0.0 0.0.0.0 255.255.0.0 U 0 0 0 eth0
192.168.1.0 0.0.0.0 255.255.255.0 U 0 0 0 eth1
Press ENTER to continue
14- Ping Service
Main Menu → Diagnostics Services → Ping Service
...
Make selection: 14
================ Ping Services ==============
ElecSys(V:5.7.2017-08-24-1000) Mon Dec 20 05:22:35 1999
DNPMastTest : 1 @ 10.63.191.28 REDIGATE-400 <38258-0025>-SerialNumb
---------------------------------------------
Enter Host to Ping (IP-Addr or Name) 10.63.191.29
!!!! Press CTRL-C to stop pinging !!!!
PING 10.63.191.29 (10.63.191.29): 56 data bytes
64 bytes from 10.63.191.29: seq=0 ttl=64 time=2.360 ms
64 bytes from 10.63.191.29: seq=1 ttl=64 time=1.295 ms
64 bytes from 10.63.191.29: seq=2 ttl=64 time=1.293 ms
^C
--- 10.63.191.29 ping statistics ---
3 packets transmitted, 3 packets received, 0% packet loss
round-trip min/avg/max = 1.293/1.649/2.360 msm
s
15- RTDB Status
Main Menu → Diagnostics Services → RTDB Status
...
Make selection: 15
================ RTDB Status ==============
ElecSys(V:5.7.2017-08-24-1000) Mon Dec 20 05:40:14 1999
DNPMastTest : 1 @ 10.63.191.28 REDIGATE-400 <38258-0025>-SerialNumb
---------------------------------------------
Chan Addrs Unit Dbg Time Wrote To NumWrite RBE(0) RBE(1)
---- ----- ---------------- --- ----------- -------- -------- ------ ------
0 1 DNP3 Field Unit ON 1 00:00:00 0 0 0 0
1 1 DNP3 Field Unit ON 30 00:01:04 40001 1 0 0
15 3 Virtual ON 1 00:00:00 0 0 0 0
Redisplay (Y/N)
?
The information included in this display is:
...
Make selection: 16
================ RTDB Diags ==============
ElecSys(V:5.7.2017-08-24-1000) Tue Dec 21 03:54:15 1999
DNPMastTest : 1 @ 10.63.191.28 REDIGATE-400 <38258-0025>-SerialNumb
---------------------------------------------
Chan Name Status Rtus Time
==== ============== ======== ==== ==================
0 Channel0 w/Errors 1 Tue Dec 21 03:54:12 1999
1 Channel0 w/Errors 1 Tue Dec 21 03:54:15 1999
15 Channel15 Normal 1 Tue Nov 30 06:00:02 1999
Enter Channel (0 to 15) ?
0
...
NOTE: the Debug Level applies to all enabled Field Units under this Master Channel. (To see diagnostics for only some Field Units on a channel, you must disable diagnostics on the other units.)
Valid Debug Level:
0 - Fatal Errors (Ending)
1 - General Errors (Error)
2 - Status Messages (Status)
3 - Data Display (Display)
4 - Data Dump (Dump)
Debug Level 0-4 ?
4
...
-----------------RTU---------------- -----POLL------- -------ERRORS-------
Addr Name Protocol Status Time Count TimOut BadData Frame
----- ---------------- -------- -------- -------- -------- ------ ------- -----
1 DNP3 Field Unit DNPMST00 Timeout 03:54:19 0 391487 0 0
Enter RTU Address (-1 for all) ? 1
Enter 0=Disable : 1=Enable [Default=1] ? 1
Setting RTDB-Rtu 1 to Enable Dump
Press ENTER
Valid Debug Level:
0 - Fatal Errors (Ending)
1 - General Errors (Error)
2 - Status Messages (Status)
3 - Data Display (Display)
4 - Data Dump (Dump)
Debug Level 0-4
?
...
Make selection: 17
================ MQtt Client(s) Status ==============
ElecSys(V:5.7.2017-08-24-1000) Mon Dec 20 05:40:14 2016
DNPMastTest : 1 @ 10.63.191.28 REDIGATE-400 <38258-0025>-SerialNumb
---------------------------------------------
ConnectState : ConnectedBroker IP Addr : 127.0.0.1 - 8883
Number Connects : 20
Bytes Received : 205
Bytes Sent : 80121
Messages Receive: 43
Messages Sent : 26026
QOS-0 Sent : 472
QOS-1 Sent : 0
QOS-2 Sent : 0
Last Send Time : 12/20/2016 05:39:49
Last Recv Time : 12/20/2016 01:54:35
Last Recv Topic : sys/GroupID/RediGate/FieldUnit1
Last Sent Topic : RBE/GroupID/RediGate/Channel/FieldUnit1
MQidspX0 was not found...
MQidspX1 was not found...
Redisplay (y/n
)?
18- RTDB Data Dump
...
Make selection: 18
================ RTDB Dump ==============
ElecSys(V:5.7.2017-10-25-1700) Mon Nov 6 18:19:21 2017
UnitName : 1 @ 192.3.1.10 REDIGATE-400 <38258-0025>-SerialNumb
---------------------------------------------
Chan Name Status Rtus Time
==== ============== ======== ==== ==================
0 Channel0 Normal 2 Mon Nov 6 18:19:19 2017
15 Channel15 Normal 1 Mon Nov 6 18:18:14 2017
Enter Channel Number ? 0
-----------------RTU---------------- -----POLL------- -------ERRORS-------
Addr Name Protocol Status Time Count TimOut BadData Frame
----- ---------------- -------- -------- -------- -------- ------ ------- -----
2 Modbus02 MBMAST00 Timeout 18:19:14 0 4 0 0
3 Modbus03 MBMAST00 PollDone 18:19:22 384 0 0 0
Enter Rtu Address
3
The RTDB configuration is then shown for the Channel and RTU address. Enter the Starting Point Address and the Point Count of registers to display. Make sure that the quantity requested doesn't exceed the number of available registers.
Data Type Count Address
---------- ----- -------
BOOLEAN 10 1
BOOLEAN 10 10001
SINT16 5 30001
UINT16 5 40001
UINT32 5 41001
REAL32 5 42001
STRING-32 5 43001
STRING-256 5 44001
Enter Starting Point Address 1
Enter Point Count (1 to 125 or only 16 STRING-256) 50 5
0
After entering the Point Count, the register values will be displayed in hexadecimal format.
Data type is Boolean (HEXADECIMAL)
1)- 01 00 00 01 00 00 01 00
9)- 01 00 00 00 01 00 01 01
10007)- 00 01 00 01 0001 ffec 7fff f060
30005)- ffff 000a 00c8 0bb8 9c40 ffff 00002710 00030d40
41003)- 002dc6c0 02625a00 7fffffff 3f800000 c1a00000 40490fdb cc189680 5cde0b6b
43001)- 00656e6f 006f7774 65726874 72756f66 34333231 00454e4f 004f5754 45524854
44004)- 52554f46
455649464556494
6
Enter Y (Yes) to refresh the display of the register values or N (No) to exit the display.
Enter F to display the RTDB values formatted according to the data type configured for each register. In the example below, the following registers are shown:
Registers | Data Type |
1-10, 10001-10010 | Boolean |
30001-5 | SINT16SINT16S |
40001-5 | UINT16 |
41001-5 | UINT32 |
42001-5 | REAL32 |
43001-5 | STRING32 |
44001-5 | STRING256 |
Redisplay (Y/N/F/H/B/O/A where F=Formatted, H=Hex, B=Bin O=Online A=Auto) ? f
Data type is Boolean (FORMATTED)
1)- ON OFF OFF ON OFF OFF ON OFF
9)- ON OFF OFF OFF ON OFF ON ON
10007)- OFF ON OFF ON 1 -20 32767 -4000
30005)- -1 10 200 3000 40000 65535
41001)- 10000 200000 3000000 40000000 2147483647
42001)- 1.00000 -20.0000 3.14159 -4.00000e+07 5.00000e+17
43001)- <one > <two >
)- <three > <four >
)- <1234567890123456789012345678901 >
44001)- <ONE>
<TWO>
<THREE>
<FOUR>
<FIVE>
<FIVE
>
Enter H (Hex) to show the values as hexadecimal again. Enter B (Binary) to show Boolean registers as "1" or "0".
...
Redisplay (Y/N/F/H/B/O/A where F=Formatted, H=Hex, B=Bin O=Online A=Auto) ? o
Data type is Boolean (ONLINE/offline)
1)- ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE
9)- offline offline ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE
10007)- ONLINE ONLINE offline offline ONLINE ONLINE ONLINE ONLINE
30005)- ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE
41003)- ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE
43001)- ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE ONLINE
44004)- ONLINE ONLINE ONLIN
E
Enter A (Auto) to automatically refresh the values of the RTDB registers using the current display format. Enter a number of Seconds for how often to redisplay.
Redisplay (Y/N/F/H/B/O/A where F=Formatted, H=Hex, B=Bin O=Online A=Auto) ? a
Enter Number of Seconds between updates (1 to 60) 3
Data type is Boolean (FORMATTED) 11/7/2017 1:06:36
1)- ON OFF OFF ON OFF OFF ON OFF
9)- ON OFF OFF OFF ON OFF ON ON
10007)- OFF ON OFF ON 1 -20 32767 -4000
30005)- -1 10 200 3000 40000 65535
41001)- 10000 200000 3000000 40000000 2147483647
42001)- 1.00000 -20.0000 3.14159 -4.00000e+07 5.00000e+17
43001)- <one > <two >
)- <three > <four >
)- <1234567890123456789012345678901 >
44001)- <ONE>
<TWO>
<THREE>
<FOUR>
<FIVE>
Enter any of the other letter options to stop the automatic RTDB display.
...
This is a legacy menu for the DialBackup task, which is currently not supported in the RediGate.
Anchor | ||||
---|---|---|---|---|
|
...
Enter 99 for Monitor Diagnostics.
510- Trend a Point
535- View Custom Rpt
If one or more Custom Report is configured for this RediGate, view the contents of the report. The Custom Report is a pre-defined set of RTDB registers with a tag descriptor. This is a more convenient way to view the values of registers than option 18, and it allows registers that have been defined as read/write to be written to through the user menu.
Enter 535 for View Custom Rpt.