- Using ACE, Open the default configuration you used in the "Getting Started Guide".
Download and open RediGate-Scaling-Demo.xml from the http://redigate.elecsyscorp.com/examples site within the same ACE window as your default configuration.
The example is located under Other Example Configurations → Math/Scaling Example Configuration.- If you have already completed one of the other example configurations to obtain a "SimData" field unit with simulated data, you may skip to the next numbered step.
-
- In this example, register 39101 contains a divisor for the 3rd calculation (2018 / 100 = 20.18).
To change the scaling factor:
Enter 'B' to move the cursor to the last entry.
Enter 'C' to change the register value.
Enter the new divisor.
Enter 'Y' to write the value into the register.E'xit N'ext P'rev T'op B'ottom H'elp 'C'hange(Ch14/Rtu1/@39101) 7/7 c
EDIT Chan14/Rtu1/39101 (*39101) IEEE[100] 10
(10) for Chan14/Rtu1/39101 (*39101)....
...End of List...Okay to write current entries? (y/n) y
The new scaling factor should appear in the list, and the register 44001 should be divided by the new number.*30003=2018 *44001=201.8
>*39101=10
...
Original value SimData register | Copied value ScaledUnit register | Mathematical Operations | Modified value ScaledUnit register | Modified value SimData register |
---|---|---|---|---|
44005 (Minutes) → | 30001 | *9 /5 + 32 (convert C to F) | 40001 → | 44011 |
44006 (Seconds) → | 30002 | *1000 /3 | 40002 → | 44012 |
44001 (Year) → | 30003 | divide by register 39101 | 44001 → | 46011 |
The Poll Table in the "Math-Scaling Demo Unit" copies data from the source field unit (channel 15 unit 2) to the local (ScaledUnit) RTDB registers.
Then the Poll Table calls POD number 12 for all the mathematical functions, and then copies the resulting values back to the original source unit ("SimData").
The logic contained in POD #12 is shown in the following screen capture. For each of the three data values,
...
These final registers are copied back to the original Field Unit by the Poll Table rows, described above.
Info |
---|
NOTE: Be aware that register data types will affect the calculations. For instance:
Be careful not to copy the modified values back into the same registers as the original source value – this will cause irregularities as the original value and modified value are alternately stored into the same register. |
...
This configuration gives just a few examples of how POD logic may be used to modify data in the RediGate. For illustration, it is shown as a separate channel for performing the math functions.
But for configurations that contain data in an existing Internal Master unit (such as "SimData"), the new POD function could have instead been added to the existing Field Unit to modify data right in the RTDB, without requiring the registers to be copied to and from the ScaledData unit using a Poll Table.
See the POD Programming Manual for more details on using POD logic statements.