Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...


The Master Channel must have at least one child Circuit object defined (Async or Network).

PropertiesValues
Name

Enter the Master Channel name.

This is the name which appears in the user diagnostics menu, and is also see in an HCP diagnostic window if used with Elecsys HCP. 

Channel Type

In some configurations this may be listed as "Direct Master", which includes a few operational differences noted below. The main differences between the Channel Types are listed below:

Direct Master 

  • Global Scan Period
  • One failed poll changes RTU comms status.

Direct Master Flex Scan1.Global

  • Scan Period
Scan Period
  • configured for each scan.
2.One failed poll changes
  • All "effective" polls must fail before 
RTU comms status.
  • RTU comms status fails. 
Auto Start

Select the automatic polling method for the channel.

Automatic polling types supported are:

  • Yes – polling started automatically upon power-up
  • No – polling started manually through the MMI
  • Link Based Poll – polling is started only after a P/R connection has been made from an HCP. 
Response Timeout

Enter the response timeout in milliseconds.

Time in milliseconds to wait for a poll response before declaring the message failed.

For Network Circuits, if a scan fails because the socket is broken or interface is unavailable, then the Master Channel protocol will wait a period of time (Response Timeout * 2) to try the next IP address in the Circuit. 

Broadcast Delay

Enter the broadcast delay in milliseconds. When a host computer sends a command to a field unit via the Master Channel, some field units do not want to be polled again for a certain amount of time to allow processing the command. This option allows normal polling to be delayed temporarily.

Delay in milliseconds after a command is sent to the field device before normal polling resumes. Normally this can be left to the default of 0. 

Interpoll delay

Enter the interpoll delay in milliseconds. Use this to add a delay between each poll sent by the channel to any field unit.

Time in milliseconds to wait between each poll. 

Scan Effective Limit

The Scan Effective Limit is the time (in seconds) defining which scans in the Scan Table are considered "effective" – meaning, polls which affect the status of the Field Unit if there are poll failures. Scan Table entries which have a Scan Period greater than the Scan Effective Limit do not mark the Field Unit offline when the scan fails.

For instance, if the Scan Effective Limit is configured for 30 seconds, then any scans defined with Scan Period <= 30 will be used to mark the Field unit online or offline. Scans with Scan Period greater than 30 will not mark the Field Unit offline even if they fail. The Scan Effective Limit only applies to the "Direct Master Flex Scan Table" version of the channel object.

A Scan Effective Limit of 0 disables this feature, thus all polls will affect the Field Unit status. 

Network Recovery

Enter the network recovery period in seconds.

Time period to wait after an RTU fails, before attempting to re-establish communications with that RTU. This will take the device off scan, allowing other devices on the channel to be polled more frequently and not waste as much time retrying a failed device. 

Scan Table

Click the Edit Table button to define the order and selection of polls to be sent to all field units on this channel, independent of protocol. Field Unit configurations (Modbus, etc.) define the protocol-specific nature of the individual polls that are sent. 

Scan Table details:

Unit Address - This is the Field Unit Address as configured in each field unit on this Channel. (To force the Scan Table to ignore the Scan Period, enter a Scan Table row with the Unit Address of -1.) 

Poll Record - This is the row number in the Poll Record in the Field Unit definition. The first row in a Poll Table is referenced as record 1. Only those polls which are to be polled continuously need to be listed in this Scan Table. 

Scan Period - Enter the scan period in seconds. The Scan Period is the amount of time to use for scheduling each scan (global for all scans in the Direct Master, or configured per scan row in the Direct Master Flex Scan Table). 

For the Direct Master, the channel will restart the scan table sequence after the Scan Period has expired. If the total time for a given channel exceeds the scan period, the next scan shall be scheduled immediately.

For the Direct Master Flex Scan Table, each poll is scheduled based on its own Scan Period. If the total time required for scans at any point is greater than allowed by the Scan Periods, the scans will operate as fast as possible. 

Setting a Scan Period to a negative number will disable a scan. However, the first entry in the Scan Table for each Unit Address should not be disabled, or it may not correctly set the Alive/Dead status of the unit. 

Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration.

Async Circuit

An Async Circuit is a serial communications path to one or more field units from a common Master Channel, using an Async serial port. The Async Circuit allows for redundant serial ports to a common set of field units, such as a Primary and Secondary radio or modem communication path.

...

PropertiesValues
Primary Port

Select the primary physical communication port for this circuit. 

The selected port must be defined as an object under Networks, where its Async port properties (baud rate, etc.) are also defined (see the section Async Port).

The same port (e.g. COM1) may also be shared with certain other tasks, such as Terminal Server, and may be used with Virtual Ports.

 

Network Circuit

A Network Circuit is an IP network communications path to one or more field units from a common Master Channel. The Network Circuit is used when the field unit is connected via a network, such as TCP/IP, PPP, or SLIP.

...

PropertiesValues
Unit Name

Enter the field unit name.

Unit name is displayed in diagnostic menus and in an HCP diagnostic screen.  

Unit Address

Enter the actual field unit address which is configured in the device being polled.

Valid Modbus addresses 1 to 255.

FieldUnit - Modbus Master (and others)

...

PropertiesValues
Database Definition

Click the Edit Table button to edit the details of the RTDB definition.

Point Count – Enter the number of data points of this type to be allocated space in the database.

Field Format – Select the point data format:

Boolean – Boolean
UINT8 – Unsigned 8-bit integer (0 to 255)
SINT16 – Signed 16-bit integer (-32,768 to 32,767)
UINT16 – Unsigned 16-bit integer (0 to 65,535)
SINT32 – Signed 32-bit long integer
UINT32 – Unsigned 32-bit long integer
REAL32 – IEEE floating point (32-bit)
STRING32 – Each field contains up to 32 ASCII characters
STRING256 – Each field contains up to 256 ASCII characters
EVENT – Timestamped event data obtained from field device.

The following field formats are the same as the above but do not generate an RBE flag when the data changes, even if the Field Unit is set to Produce RBEs=Yes.

No-Rbe Boolean – Boolean
No-Rbe UINT8 – Unsigned 8-bit integer (0 to 255)
No-Rbe SINT16 – Signed 16-bit integer (-32,768 to 32,767)
No-Rbe UINT16 – Unsigned 16-bit integer (0 to 65,535)
No-Rbe SINT32 – Signed 32-bit long integer
No-Rbe UINT32 – Unsigned 32-bit long integer
No-Rbe REAL32 – IEEE floating point (32-bit)
No-Rbe STRING32 – Each field contains up to 32 ASCII characters
No-Rbe STRING256 – Each field contains up to 256 ASCII characters

Data Address – Enter the address of the starting register within the RTDB for the Field Format and Count defined on this row.
The RTDB fields must be defined so they are non-overlapping, and there need to be enough data points defined to hold all of the data returned in the Poll Table entries defined for this FieldUnit.
All RTDB database fields (except String types) may hold 32-bit data items, regardless of the data type or address. The RTDB typically uses registers defined in the range of Modbus addresses, although this is not a strict requirement. However, if the RTDB is connected to a Modbus Slave Channel, it does require Modbus addressing to work properly as a slave (see the Modbus Slave Channel documentation).

Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration.

...

AttributesFunction
Object TypeLinuxDeadband
Parent(s)System → Clients → Master Channels → Master Channel → Circuit → Field Unit → RTDB
InstanceMust be 0
PropertiesValues
Deadband

Click the Edit Table button and add as many rows as necessary to define the desired deadband values for the points in the RTDB.

  • Field(Row) – Enter the row number of the field in the RTDB, containing the data point. RTDB row numbers start at 1.
  • Offset – Enter the offset into data point address referenced in the field. Offset of 0 refers to the first point number in the RTDB field.
  • Count – Enter the number of data points that the deadband limit will be applied to.
  • Deadband – Enter the deadband value, which is the amount a value in the RTDB can change before it will be flagged as an RBE. Deadband value is entered as an integer or floating point value, which is handled as an 11-character (max) string. If IEEE floating point format is used, its entry must include a decimal point (such as 11.0).
 
  • Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration. 

For example, let's say the RTDB is configured with the following fields:

...

PropertiesValues
Init ValuesClick the Edit Table button to define any pre-initialized RTDB values. 
  • Data Address – Enter the starting register number to define default values. This should be a register number that is defined as part of the RTDB. 
  • Count – Enter a count of registers, beginning with Data Address, that should be initialized to the same value. 
  • Init Value – Enter the value to which the register(s) will be initialized on startup. For Boolean registers, enter a '0' or '1' initial value. For floating point registers, enter the initial value in floating point format. 
  • Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration.

 

Tag Names

 

RTDB database locations are configured using numeric address locations. However, the optional Tag Names child object under the RTDB allows one or more numeric address to be associated with an ASCII tag. This may be used for publishing data by tag using MQTT, for internal display using Custom Reports, and they may be used for other purposes.

...

PropertiesValues
Init Values 

Click the Edit Table button to define any RTDB tags. 

  • Register Address – Enter the RTDB register address in the parent RTDB object. 
  • Tag Name – Enter an ASCII tag (up to 32 characters). Do not use the following characters: "|" (pipe), "\" (backslash), and "," (comma). Space characters in the tag are converted to underscores.
  • Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration.

 

Include Page
Tag Name Substitutions
Tag Name Substitutions

...

PropertiesValues
Block Definition

Click the Edit Table button to add as many rows as necessary to define the Data Block capability.

  • Data Address – Enter the register number of the beginning of each block. This should be a register number that is defined as part of the RTDB.
  • Point Count – Enter the number of data points to group together in each block. Ensure the Point Count is not defined larger than the available points in the RTDB field. Data blocking currently supports a contiguous block of data registers using a range of different data types (Boolean, UINT16, UINT32, REAL32), but cannot be used on larger data types (Strings, 64-bit data).
  • Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration.
Parent(s)System → Clients → Master Channels → Master Channel → Field Unit → RTDB
InstanceMust be 0

...

PropertiesValues
Reserved

Unused field 

Timestamp

Click the Edit Table button to add as many rows as necessary to define the Timestamp operation. 

Poll Number – Enter the row number of the poll defined in the unit's Poll Table.

Whenever this poll occurs for the defined points (or when any changed data points are stored in the RTDB field), a timestamp is also stored. Poll numbers start at 1. 

Stamp Address – Register address within the RTDB for this Field Unit in which to store the timestamp value for this poll.

The Stamp Address should be the first of one or more registers with a UINT16 or UINT32 data type, and must be defined in the RTDB with the correct quantity and type. Make sure that each register or registers occupied by the timestamp are not overwritten by any other data value to avoid conflicting data.

Stamp Format – Data format to use when storing data into the specified register (UINT16 or UINT32). 

The Stamp Format should be chosen appropriately to match the Stamp Type (below), and the data type of the RTDB register. UINT24 or UINT32 data types should be stored into a UINT32 RTDB register.

    • UINT16
    • UINT32
    • UINT64 (seconds*1000 + mSec from 1969 if Packed, else 1979)

Stamp Type – Format in which to store the timestamp.

  • 32 bit centi-seconds (1 reg, Always) - Store timestamp at the time each poll is initiated, as a 32-bit number as centi-seconds (10's of milliseconds) since the last startup.
  • 32 bit seconds + mSec (2 reg, Always) - Store timestamp at the time each poll is initiated, as two 32-bit numbers (seconds since January 1, 1980; and milliseconds).
  • YYYY,MM,DD,HH,mm,ss,mSec (7 reg, Always) - Store timestamp at the time each poll is initiated, as seven 16-bit registers containing year, month (1-12), day (1-31), hour, minute, second, milliseconds.
  • 32 bit centi-seconds (1 reg, Post-Deadband) - Store timestamp only on changed RTDB data, as a 32-bit number as centi-seconds (10's of milliseconds) since the last startup.
  • 32 bit seconds + mSec (2 reg, Post-Deadband) - Store timestamp only on changed RTDB data, as two 32-bit numbers (seconds since January 1, 1980; and milliseconds).
  • YYYY,MM,DD,HH,mm,ss,mSec (7 reg, Post-Deadband) - Store timestamp only on changed RTDB data, as seven 16-bit registers containing year, month (1-12), day (1-31), hour, minute, second, milliseconds. 

Comment - Optional column, allowing a descriptive comment to be entered for each row in the table. The Comment field is unused in the configuration.