Problem

The RediGate does not seem to accepting accept the parameters of the latest configuration that was loaded. 

Possible Causes

  1. If you downloaded a configuration to the RediGate and left the "Deploy Immediately" button unchecked, you will need to power cycle the RediGate or manually run the "reconfigure" command in order for the RediGate to deploy the downloaded configuration.

  2. If you fail to deploy the uploaded configuration prior to download a new configuration with a different name, you will end up with multiple configurations in the RediGate's /home/director or /home/Dirupld directories. The RediGate expects only one configuration to be in either of these directories when it is rebooted or reconfigured, so having multiple configurations in a directory causes the RediGate to ignore the both new uploaded configurations and keep its current configuration. If this occurs, the RediGate will log the error to the "Problem.txt" file.

     

 

Symptoms

  1. Problem.txt file information shows the following errorerror below (see Accessing Log Files for info on accessing the Problem.txt file):

     

    Code Block
    titleProblem.txt File
    
    Multiple .xml.gz files cannot be translated
    RG-400C-22_Ethernet_IP_Forwarding_V4.xml.gz  and  RG-400C-22_Ethernet_IP_Forwarding_V7.xml.gz
    Press ENTER...
    
    


  2. If there There are 2 .xml.gz's (not including .run) If there are 2 .uff's (not including .run)listed in the download directory:
    Image Added
  3. The name of the configuration on the RediGate does not match the name of the last configuration that was downloaded to it
  4. If you need more detailed information about the status of the MQTT client, you can enable diagnostics by entering options 3, 6, 3, 4:
    Image Removed
  5. After entering those values, press <enter> a few times to get back to the main menu, and then enter options 3, 99, y, <enter>
    Image Removed
  6. The terminal will output all of the diagnostics data from MQTT client task. You can enable/disable other task diagnostics be following step 1 and entering option 3, 6, (task number of interest), 4.  Press <enter> to pause the flow of the diagnostics data, and "X" to exit. 

      Possible Causes

      1. A configuration already exists on the RediGate, and the 

      Solutions

      1. Check to see that the name of the configuration matches 

      Viewing the MQTT Status

      1. In the RediGate command-line session, select "3" (for Diagnostic Services) and then "17" (for MQTT Status):
        Image Removed
      2. Here you will see various diagnostic information about the current connectivity status of the RediGate

      Viewing the MQTT Diagnostics

        1. Include Page
          Checking a RediGate's Current Configuration
          Checking a RediGate's Current Configuration

      Solution

      Option 1: Manually delete all of the old .xml.gz files in the download directory using the RediGate MMI

      Image Added

      Option 2: Manually delete all of the old .xml.gz files using Linux commands by logging in as root user

      Image Added